Representative photo. Please check item description for details.

EPI SERIES 7240 Thermal Mass Flow Switch, 12" PROBE INSERTION

https://www.branom.com/web/image/product.template/185858/image_1920?unique=7cf654a
(0 review)

Manufacturer: Eldridge Products - EPI

Mfg Product Code: 7240-INT-SSS-000-AC115-MW050-4012NA-NA

Weight: 10.0 lb(s)

On Hand: 0

7240 = Flow Switch Insertion Style - 1/2" OD Probe
INT = Integral Electronics - standard outputs: 0-5VDC & 4-20mA (flow with optional temperature), RS485
ModbusRTU. 4-20mA FLOW enabled unless specified. Modbus is disabled.
SSS = 316L stainless steel sensor. OPTIONAL - sensor with attenuating rod, sensor with particle sensor
shield, or Hastelloy® C-276 sensor
000 = No Display
AC115 = 115VAC 50/60HZ
4012NA = 1/2" OD x 12" Probe
NA = No Agency Approvals
Trip point accuracy (Ref: 21°C)……………………..........................……1% of set point
Signal output Relay Contact High & Low……....…..........................…6 AMP @ 24VDC or 250VAC (Class A
Insulation)
Event Relay Rating…………………………………………..............................One with Frequency or Two, 1 AMP @
30VDC (33W)
Trip point accuracy......................................................................................1.0% of set point
Repeatability....................................................................................................0.5% of Full Scale
Sensor response time..................................................................................1 second
Turn down ratio..........................................................................................100:1 minimum
Range (gas).....................................................................................................0 - 15,000 SFPM / 0 - 4,572 NMPS
Range (liquid)................................................................................................0 - 300 SFPM / 0 - 91 NMPS
Electronics temperature range.............................................................0 to 50°C (32 to 122°F), extended range
optional
Fluid temperature range........................................................................-40 to 200°C (-40 to 392°F), extended
range available
Gas temperature range...........................................................................-40 to 200°C (-40 to 392°F), extended
range available
Gas pressure effect (liquid not applicable).....................................Negligible over 20% of set point pressure
Pressure rating maximum.......................................................................500 PSI - standard, >500 PSI - special
Input power requirement........................................................................24VDC @ 250mA
115VAC 50/60 Hz optional
230VAC 50/60 Hz optional
Flow Transmitter power requirements............................................5 Watts maximum
Flow Switch enclosure..............................................................................NEMA 4X, Class 1, Div 1, Groups B, C and
D - standard
Wetted materials.........................................................................................316L Stainless Steel (Hastelloy optional)
Standard Temperature and Pressure (STP)....................................70°F & 29.92" Hg (Air Density = 0.75
lb/ft3)

  • Brand_Name
  • Measurement Minimum
  • Input Communication Protocol
  • Output Communication Protocol
  • Input Voltage
  • Ingress Protection
  • NEMA / UL

This combination does not exist.

EPI SERIES 7240 Thermal Mass Flow Switch, 12" PROBE INSERTION

  • Brand_Name
  • Measurement Minimum
  • Input Communication Protocol
  • Output Communication Protocol
  • Input Voltage
  • Ingress Protection
  • NEMA / UL

1,642.24 1642.24 USD 1,642.24

1,642.24

Not Available For Sale

This combination does not exist.


7240 = Flow Switch Insertion Style - 1/2" OD Probe
INT = Integral Electronics - standard outputs: 0-5VDC & 4-20mA (flow with optional temperature), RS485
ModbusRTU. 4-20mA FLOW enabled unless specified. Modbus is disabled.
SSS = 316L stainless steel sensor. OPTIONAL - sensor with attenuating rod, sensor with particle sensor
shield, or Hastelloy® C-276 sensor
000 = No Display
AC115 = 115VAC 50/60HZ
4012NA = 1/2" OD x 12" Probe
NA = No Agency Approvals
Trip point accuracy (Ref: 21°C)……………………..........................……1% of set point
Signal output Relay Contact High & Low……....…..........................…6 AMP @ 24VDC or 250VAC (Class A
Insulation)
Event Relay Rating…………………………………………..............................One with Frequency or Two, 1 AMP @
30VDC (33W)
Trip point accuracy......................................................................................1.0% of set point
Repeatability....................................................................................................0.5% of Full Scale
Sensor response time..................................................................................1 second
Turn down ratio..........................................................................................100:1 minimum
Range (gas).....................................................................................................0 - 15,000 SFPM / 0 - 4,572 NMPS
Range (liquid)................................................................................................0 - 300 SFPM / 0 - 91 NMPS
Electronics temperature range.............................................................0 to 50°C (32 to 122°F), extended range
optional
Fluid temperature range........................................................................-40 to 200°C (-40 to 392°F), extended
range available
Gas temperature range...........................................................................-40 to 200°C (-40 to 392°F), extended
range available
Gas pressure effect (liquid not applicable).....................................Negligible over 20% of set point pressure
Pressure rating maximum.......................................................................500 PSI - standard, >500 PSI - special
Input power requirement........................................................................24VDC @ 250mA
115VAC 50/60 Hz optional
230VAC 50/60 Hz optional
Flow Transmitter power requirements............................................5 Watts maximum
Flow Switch enclosure..............................................................................NEMA 4X, Class 1, Div 1, Groups B, C and
D - standard
Wetted materials.........................................................................................316L Stainless Steel (Hastelloy optional)
Standard Temperature and Pressure (STP)....................................70°F & 29.92" Hg (Air Density = 0.75
lb/ft3)


Brand_Name:Eldridge
Measurement Minimum:0
Input Communication Protocol:4-20 mA, 2 Wire
Output Communication Protocol:4-20 mA / HART
Input Voltage:120 VAC
Ingress Protection:IP66
NEMA / UL:NEMA 4X


Specifications

Brand_Name Eldridge
Measurement Minimum 0
Input Communication Protocol 4-20 mA, 2 Wire
Output Communication Protocol 4-20 mA / HART
Input Voltage 120 VAC
Ingress Protection IP66
NEMA / UL NEMA 4X